DSpace Repository

Air curtains combined with smoke exhaust for smoke control in case of fire: Full-size experiments

Show simple item record

dc.contributor.author Viegas, J. pt_BR
dc.contributor.author Teixeira da Cruz, H. pt_BR
dc.date.accessioned 2018-12-28T15:19:07Z pt_BR
dc.date.accessioned 2019-02-07T15:13:52Z
dc.date.available 2018-12-28T15:19:07Z pt_BR
dc.date.available 2019-02-07T15:13:52Z
dc.date.issued 2018-11-07 pt_BR
dc.identifier.citation https://doi.org/10.1007/s10694-018-0786-z pt_BR
dc.identifier.uri https://repositorio.lnec.pt/jspui/handle/123456789/1011203
dc.description.abstract This paper analyses the possibility of using air curtains to prevent smoke flow from fire compartments. Full size experiments have been carried out and several relevant conditions to assess smoke-tightness have been tested. The smoke temperature during the tests was ranging from 182ºC to 351ºC, the angle measured between the curtain axis and the vertical plane was ranging from 18º and 26º, the nozzle thickness was ranging from 0.017 m to 0.045 m and the velocity at the nozzle was ranging from 8.3 m/s to 19.9 m/s. During the tests, the air curtain’s nozzle was positioned horizontally at the top of a permanent opening (door). With this configuration, we obtained an approximately vertical downward jet through the used opening. This paper includes the final results of the tests and develops an analytical tool for predicting the performance of air curtains. It was concluded that it is possible to achieve smoke-tightness, provided that the adequate plane jet parameters and the compartment’s smoke exhaust are correctly adjusted. According to this analysis, the smoke-tightness limit corresponds to equation B=〖ΔP〗_a⁄〖ΔP〗_s =-0.30 u_a⁄u_(a_min) +1.25 (with 1.30≤ u_a⁄u_(a_min) ≤1.67). pt_BR
dc.language.iso eng pt_BR
dc.publisher Springer pt_BR
dc.relation QREN no. 23226 - Smoke Shield pt_BR
dc.rights restrictedAccess pt_BR
dc.subject Smoke control pt_BR
dc.subject Plane jets pt_BR
dc.subject Full size experiments pt_BR
dc.subject Vertical air curtains pt_BR
dc.title Air curtains combined with smoke exhaust for smoke control in case of fire: Full-size experiments pt_BR
dc.type workingPaper pt_BR
dc.identifier.localedicao United States pt_BR
dc.description.pages 22p pt_BR
dc.description.sector CIC/CHEFIA pt_BR
dc.description.magazine Fire Technology pt_BR
dc.contributor.peer-reviewed SIM pt_BR
dc.contributor.academicresearchers SIM pt_BR
dc.contributor.arquivo NAO pt_BR