DSpace Repository

Validation of EnergyPlus thermal simulation of a double skin naturally and mechanically ventilated test cell

Show simple item record

dc.contributor.author Mateus, N. pt_BR
dc.contributor.author Pinto, A. pt_BR
dc.contributor.author Graça, G. pt_BR
dc.date.accessioned 2014-07-26T18:58:35Z pt_BR
dc.date.accessioned 2014-10-10T09:19:08Z pt_BR
dc.date.accessioned 2016-06-21T10:04:00Z
dc.date.available 2014-07-26T18:58:35Z pt_BR
dc.date.available 2014-10-10T09:19:08Z pt_BR
dc.date.available 2016-06-21T10:04:00Z
dc.date.issued 2014-02-12 pt_BR
dc.identifier.uri https://repositorio.lnec.pt/jspui/handle/123456789/1006301
dc.description.abstract This paper presents a thermal simulation validation study of the typical precision that a trained thermal simulation engineer can expect to obtain for the simulation of a room connected to a naturally ventilated double skin facade. The open source building thermal simulation tool EnergyPlus is used to predict air and surface temperatures in a free running weather exposed test cell. The validation approach used does not allow for fine tuning the simulation model by trial and error and includes a sensitivity analysis on the impact of different simulation options such as: number of thermal zones, ground heat transfer and accuracy of solar radiation data. The analysis of the results is consistent with the engineering application goal by focusing on standard indicators: average error, bias and difference between predicted and measured daily maximums. The results show good agreement between simulation and experiment, with an average simulation error in air and radiant temperature of1.4"C and an average daily maximum error of 2.5oC, pt_BR
dc.language.iso eng pt_BR
dc.publisher Elsevier pt_BR
dc.rights restrictedAccess pt_BR
dc.subject Thermal simulation pt_BR
dc.subject Validation pt_BR
dc.subject Double skin façade pt_BR
dc.subject Energyplus pt_BR
dc.subject Natural ventilation pt_BR
dc.subject Passive house pt_BR
dc.title Validation of EnergyPlus thermal simulation of a double skin naturally and mechanically ventilated test cell pt_BR
dc.type workingPaper pt_BR
dc.description.figures 12 pt_BR
dc.description.tables 11 pt_BR
dc.description.pages 511-522pp pt_BR
dc.description.volume 75 pt_BR
dc.description.sector DED/NAICI pt_BR
dc.description.magazine Energy and Buildings pt_BR


Files in this item

Files Size Format View

There are no files associated with this item.

This item appears in the following Collection(s)

Show simple item record

Search DSpace


Advanced Search

Browse

My Account